Introduction
Power factor (tan delta) testing detects insulation deterioration and moisture.
Test Methods
- UST (Ungrounded Specimen Test)
- GST (Grounded Specimen Test)
- Guard terminal for surface leakage
Acceptance Criteria
New transformers: < 0.5% at 20°C. Service-aged: < 1.0% (investigate if > 2%).