Power Factor Testing for Transformer Diagnostics

Introduction

Power factor (tan delta) testing detects insulation deterioration and moisture.

Test Methods

  • UST (Ungrounded Specimen Test)
  • GST (Grounded Specimen Test)
  • Guard terminal for surface leakage

Acceptance Criteria

New transformers: < 0.5% at 20°C. Service-aged: < 1.0% (investigate if > 2%).